10KV vacuum circuit breaker insulation rod
Category:
AIS AND RMU SWITCHGEAR COMPONENTS
1. The outer surface should be smooth and free of defects such as bubbles and cracks;
2. Unmarked tolerances shall be in accordance with IT14;
3. Withstand rated voltage ≥ 48kv/1min;
4. Lightning impulse ≥ 110kV.
5. Partial discharge capacity 14.4kV ≤ 5pC;
6. Tensile strength ≥ 1200N, flexural strength ≥ 120MPa
Keywords:
10KV vacuum circuit breaker insulation rod
Description
A(mm) | B(mm) | Creepage(mm) |
209 | 65 | 234 |
214 | 96 | 271 |
241 | 96 | 235 |
1. The outer surface should be smooth and free of defects such as bubbles and cracks;
2. Unmarked tolerances shall be in accordance with IT14;
3. Withstand rated voltage ≥ 48kv/1min;
4. Lightning impulse ≥ 110kV.
5. Partial discharge capacity 14.4kV ≤ 5pC;
6. Tensile strength ≥ 1200N, flexural strength ≥ 120MPa