10KV vacuum circuit breaker insulation rod
1. The outer surface should be smooth and free of defects such as bubbles and cracks; 2. Unmarked tolerances shall be in accordance with IT14; 3. Withstand rated voltage ≥ 48kv/1min; 4. Lightning impulse ≥ 110kV. 5. Partial discharge capacity 14.4kV ≤ 5pC; 6. Tensile strength ≥ 1200N, flexural strength ≥ 120MPa
Ring main unit insulation tube
1. The outer surface is smooth, free of bubbles and cracks; 2. Pdwer frequency withstand voltage≥45kv/1min; 3. Lightning shock≥110kv/1min; 4. Appartial discharge14.4kV≤5pC; 5. Capacitance value25±5pF; 6. Gas tightness test using nitrogen mass spectrometer leak detector, leak rate<5*10-8 Pa.m2/S;
1. The outer surface is smooth, free of bubbles and cracks; 2. The product adopts the EPOXY RESIN encapsulating vacuum interrupter process,The good performance of the electric performance of the pole is ensured; 3. Tolerates rated voltage≥42kv/1min; 4.Lightning shock≥85kv/1min; 5. Appartial discharge14.4kV≤5pC
Circuit Breakers – Recloser Insulators
1. The outer surface is smooth, free of bubbles and cracks; 2. The product adopts epoxy resin sealed vacuum interrupter and current transformer and voltage sensor process,The good performance of the electric performance of the pole is ensured; 3. Tolerates rated voltage≥48kv/1min; 4. lightning shock≥110kv/1min; 5. Appartial discharge14.4kV≤5pC; 6. Built-in current transformer and 2 voltage sensor